SolarNode CanadianSolar 50KTL-CT Series Inverter Datum Source

This project provides SolarNode plugin that can collect data from CanadianSolar CSI-50KTL-CT series inverters.

settings

Install

The plugin can be installed via the Plugins page on your SolarNode. It appears under the Datum category as CanadianSolar KTL-CT Inverter Data Source.

Datum structure

This datum generates a datum stream with the following properties:

Property Class Units Description
ambientTemp i C Ambient temperature
apparentPower i VA Apparent power
current_a i A AC current, phase A
current_b i A AC current, phase B
current_c i A AC current, phase C
dcPower i W DC output power
dcPower1 i W DC module 1 output power
dcPower2 i W DC module 2 output power
dcPower3 i W DC module 3 output power
dcVoltage i V DC voltage
dcVoltage1 i V DC module 1 voltage
dcVoltage2 i V DC module 2 voltage
dcVoltage3 i V DC module 3 voltage
efficiency i % Efficiency rating (0-1)
events s bit set Base-10 bit set of SunSpec-compatible event codes
fault0 s bit set Base-10 bit set of Fault codes (0-15)
fault1 s bit set Base-10 bit set of Fault codes (16-31, offset -15)
fault2 s bit set Base-10 bit set of Fault codes (32-47, offset -32)
frequency i Hz AC frequency
opState s enum Device Operating State code
permFault s bit set Base-10 bit set of Permanent fault codes
reactivePower i VAR Reactive power
temp i C Internal temperature
temp_heatSink i C Heatsink temperature
temp_transformer i C Transformer temperature
vendorEvents s bit set Base-16 bit set of all active Fault codes
voltage_a i V AC voltage, phase A-N
voltage_b i V AC voltage, phase B-N
voltage_c i V AC voltage, phase C-N
voltage_ab i V AC voltage, phase A-B
voltage_bc i V AC voltage, phase B-C
voltage_ca i V AC voltage, phase C-A
warn s bit set Base-10 bit set of Warning codes
wattHours a Wh Lifetime energy
watts i W Active power total

Here is an example datum, expressed in simplified JSON form:

{
	"created": "2023-03-16 19:46:43.195Z",
	"nodeId": 123,
	"sourceId": "/INV/1",
	"localDate": "2023-03-16",
	"localTime": "15:46",
	"temp": 44.8,
	"watts": 45800,
	"frequency": 60,
	"ambientTemp": 36.7,
	"apparentPower": 45800,
	"dcPower1": 15408.629,
	"dcPower2": 15491.25,
	"dcPower3": 15212.35,
	"dcVoltage1": 634.1,
	"dcVoltage2": 637.5,
	"dcVoltage3": 636.5,
	"dcPower": 15409,
	"current_a": 52.5,
	"current_b": 52.6,
	"current_c": 52.8,
	"dcVoltage": 636.0333,
	"voltage_a": 291.2,
	"voltage_b": 293,
	"voltage_c": 290,
	"efficiency": 0.0988,
	"voltage_ab": 505.5,
	"voltage_bc": 502.6,
	"voltage_ca": 503.1,
	"reactivePower": 3300,
	"wattHours": 600613000
}

Use

Once installed, a new CanadianSolar KTL-CT Series Inverter component will appear on the Settings page on your SolarNode. Click on the Manage button to configure devices. You'll need to add one configuration for each device you want to collect data from.

Overall device settings

Each device configuration contains the following overall settings:

Setting Description
Schedule A cron schedule that determines when data is collected.
Service Name A unique name to identify this data source with.
Service Group A group name to associate this data source with.
Modbus Connection The service name of the Modbus port to use.
Modbus Unit ID The ID of the Modbus device to collect data from, from 1 - 255.
Sample Maximum Age A minimum time to cache captured Modbus data, in milliseconds.
Source ID The SolarNetwork source ID to assign to captured datum.

Overall device settings notes

Modbus Port
This is the service name of the Modbus component configured elsewhere in SolarNode. You must configure that component with the proper connection settings for your Modbus network, configure a unique service name on that component, and then enter that same service name here.
Source ID
This value unique identifies the data collected from this device, by this node, on SolarNetwork. Each configured device should use a different value.
Sample Maximum Age
SolarNode will cache the data collected from the device for at least this amount of time before refreshing data from the device again. Some devices do not refresh their values more than a fixed interval, so this setting can be used to avoid reading data unnecessarily. This setting also helps in highly dynamic configurations where other plugins request the current values from the device frequently.

Warning codes

The warn property is an enumeration of the following possible values:

Index Name Description
0 Warn0010 External fan alarm
1 Warn0020 Internal fan alarm
2 CommErr Comm error
3 Warn0030 EEPROM fault
4 Warn0040 DC side lightning protection exception
5 Warn0050 Temperature sensor anomaly
6 Warn0060 Warn0060
7 Warn0070 AC side MOV anomaly
8 Warn0080 Warn0080
9 Warn0090 Warn0090
10 Warn0100 Warn0100
11 Warn0110 Warn0110
12 Warn0120 Warn0120
13 Warn0130 Warn0130
14 Warn0140 Warn0140
15 Warn0150 Warn0150

Permanent fault codes

The permFault property is an enumeration of the following possible values:

Index Name Description
0 Fault0130 Bus sum high fault
1 Fault0120 3.3V voltage low
2 Fault0110 Bus differential high fault
3 Fault0100 Relay fault
4 Fault0090 Steady state GFCI fault
5 Fault0080 Bst hardware overcurrent fault
6 Fault0070 DCI too high fault
7 Fault0060 Bus hardware overvoltage fault
8 Fault0050 Inverter hardware overcurrent fault
9 Fault0040 Permanent fault of driver source
10 Fault0030 Fault0030
11 Fault0020 Fault0020
12 Fault0010 Permanent fault of power module
13 Fault0140 Internal hardware failure
14 Fault0150 Open loop self detection failure
15 Fault0160 Control board voltage and drive power failure

Fault codes

The vendorEvents property is a bit set of the following possible values:

Index Name Description
0 Protect0090 BUS sum high
1 Protect0080 Protect0080
2 Protect0070 BUS difference is high
3 Protect0060 Bus Soft start time out
4 Protect0050 Inverter Soft start time out
5 PVVoltageOver PV voltage over limit
6 Protect0040 PV1 High current
7 GridVoltageOutsideLimit07 Grid line voltage over limit
8 GridVoltageOutsideLimit08 Grid phase voltage over limit
9 Protect0030 Inverter current too high
10 GridFrequencyOutsideLimit High frequency of power grid
11 GridVoltageOutsideLimit11 Low frequency of power grid
12 GridVoltageOutsideLimit12 Out of phase
13 Protect0020 Grid connected relay protection
14 TempOver Over temperature protection
15 Protect0010 Inverter current bias
16 Protect0190 Protect0190
17 Protect0180 DCI current bias
18 Protect0170 DCI High current
19 IsolationErr Insulation impedance is too low
20 GFCIErr Leakage current is too high
21 Protect0160 Frequency selective anomaly
22 PVReverse PV reverse
23 Protect0150 MCU Protect
24 Protect0140 Inverter hardware over current
25 GridVoltageOutsideLimit09 Unbalanced grid voltage
26 Protect0270 Protect0270
27 Protect0130 Inverter current imbalance
28 Protect0120 Power module protection
29 ACContErr AC cont error
30 Protect0110 Bus hardware over voltage
31 Protect0100 Leakage current sensor fault
32 Protect0200 Protect0200
33 Protect0210 Internal hardware exception
34 Protect0220 Input / output power mismatch
35 PV2Reverse PV2 reverse connection
36 Protect0240 PV2 input over current
37 PV2VoltageOver PV2 voltage is too high
38 Protect0260 Anomal PV source input
39 Protect0230 Turn on the inverter Open loop detection
40 GFDIErr GFDI error
41 PV1Reverse PV1 input reverse connection
42 PV1VoltageOver PV1 voltage is too high
43 PV3Reverse PV3 input reverse connection
44 PV3VoltageOver PV3 voltage is too high
45 Protect0300 Protect0300
46 Protect0290 Protect0290
47 EmergencyStp Emergency stop

SunSpec event codes

This plugin will map specific fault codes into the SunSpec events property:

Fault Name Event Inverter Model Event
5 PVVoltageOver 1 DcOverVoltage
7 GridVoltageOutsideLimit07 10 AcOverVoltage
8 GridVoltageOutsideLimit08 10 AcOverVoltage
25 GridVoltageOutsideLimit09 10 AcOverVoltage
10 GridFrequencyOutsideLimit 8 OverFrequency
11 GridVoltageOutsideLimit11 9 UnderFrequency
13 Protect0020 2 AcDisconnect
14 TempOver 7 OverTemperature
30 Protect0110 1 DcOverVoltage
33 Protect0210 15 HwTestFailure
37 PV2VoltageOver 1 DcOverVoltage
42 PV1VoltageOver 1 DcOverVoltage
44 PV3VoltageOver 1 DcOverVoltage
47 EmergencyStp 6 ManualShutdown