This project provides SolarNode plugin that can collect arbitrary data from BACnet enabled devices. This is an advanced plugin that requires knowledge of BACnet and the BACnet configuration of the devices you want to collect data from.
By default SolarNodeOS has a built-in firewall enabled that will not allow access to arbitrary IP
ports. If using BACnet/IP, the port the BACnet network runs on (the standard port is 47808) must
be opened in the SolarNodeOS firewall, which by default is nftables and configured via the
/etc/nftables.conf file. To open port 47808, you'd add the following lines, after the existing
ones that open ports 80 and 8080:
# Allow BACnet
add rule ip filter INPUT udp dport 47808 accept
If instead iptables is used, edit the /etc/iptables/iptables.rules file and add a rule like
this:
# Allow BACnet
-A INPUT -p udp --dport 47808 -j ACCEPT
Once installed, a new BACnet Device component will appear on the Settings page on your SolarNode. Click on the Manage button to configure components.
This datum source can persist datum based on a schedule and also based on BACnet change-of-value (COV) events, if the BACnet device you're collecting data from supports COV subscriptions. The Persist Mode device setting configures this. Regardless of when datum are persisted, transient datum will be generated for each COV event and other plugins can do things with those. For example, the SolarFlux Upload plugin can post those datum to SolarFlux.
⚠️ Note that although this component is named BACnet Device Datum Source, a single component instance can be configured to read data from any number of physical BACnet devices. The term BACnet Device (upper caseD) in this guide refers to this SolarNode component, while BACnet device (lower cased) refers to a BACnet hardware/softare device this component will read data from.
This plugin provides a BACnet Device CSV Configurer component will appear on the main settings page. This component lets you upload a BACnet CSV Configuration file to configure all BACnet Device components, without having to use the component settings form.
The BACnet CSV Configuration uses the column structure detailed below,
with each row representing an individual datum property to read from the BACnet device. A header row
is required. Comment lines are allowed, just start the line with a # character (i.e. the first
cell value). The entire comment line will be ignored.
Here's an example screen shot of a configuration in a spreadsheet application. It is for two devices:
- Device
Thermwith 3 datum properties:temp,tempWater, andtempOutdoor - Device
Meterwith 2 datum properties:wattsandwattHours
Spreadsheet applications generally allows you to export the sheet in the CSV format, which can then be loaded into SolarNode via the CSV Configurer.
Individual BACnet Device components are defined by the first column (Instance ID). You can
assign any identifier you like (such as Meter, Inverter, and so on) or configure as a single
dash character - to have SolarNode assign a simple number identifier. Once an Instance ID has been
assigned on a given row, subsequent rows will use that value if the corresponding cell value is left
empty.
Here's an example of how 2 custom instance IDs Meter and Therm appear in the SolarNode UI:
The following table defines all the CSV columns used by BACnet Device CSV Configuration. Columns A - H apply to the entire BACnet Device configuration, and only the values from the row that defines a new Instance ID will be used to configure the device. Thus you can omit the values from these columns when defining more than one property for a given instance.
Columns I - Q define the mapping of BACnet object properties to datum properties: each row defines an individual datum property.
| Col | Name | Type | Default | Description |
|---|---|---|---|---|
A |
Instance ID | string | The unique identifier for a single BACnet Device component. Can specify - to automatically assign a simple number value, which will start at 1. |
|
B |
Service Name | string | An optional service name to assign to the component. | |
C |
Service Group | string | An optional service group to assign to the component. | |
D |
Source ID | string | The SolarNetwork datum source ID to use for the datum stream generated by this device configuration. | |
E |
Schedule | string | 0 * * * * * |
The schedule at which to poll the BACnet device for data. Can be either a cron value or a millisecond frequency. |
F |
Connection | string | The Service Name of the BACnet Connection component to use. | |
G |
Persist mode | string | Polling only |
Controls when to persist datum. One of Events only, Events and polling, or Polling only, or shortened to EventOnly, EventAndPoll, or PollOnly. |
H |
Sample Cache | integer | 5000 |
A maximum time to cache captured BACnet data, in milliseconds. |
I |
Device ID | integer | The BACnet device ID to collect data from. | |
J |
Object Type | string | The BACnet object type to collect data from. Can be specified as a name, like analog-input or AnalogInput, or the associated integer code, like 0. |
|
K |
Object Number | integer | The BACnet object type instance number to collect data from. | |
L |
Property ID | string | present-value |
The BACnet object property identifier to collect data from. Can be specified as a name, like present-value or PresentValue, or the associated integer code, like 85. |
M |
COV Increment | decimal | An optional change-of-value (COV) event threshold to request when subscribing to COV events, essentially filtering the COV events unless the property value has changed by at least this amount. | |
N |
Property | string | The datum property name to use. | |
O |
Property Type | enum | Instantaneous |
The type of datum property to use. Must be one of Instantaneous, Accumulating, Status, or Tag, and can be shortened to just i, a, s, or t. |
P |
Multiplier | decimal | 1 |
For numeric data types, a multiplier to apply to the BACnet value to normalize it into a standard unit. |
Q |
Decimal Scale | integer | 5 |
For numeric data types, a maximum number of decimal places to round decimal numbers to, or -1 to not do any rounding. |
Here is the CSV as shown in the example configuration screen shot above (comments have been removed for brevity):
Instance ID,Service Name,Service Group,Source ID,Schedule,Connection,Persist Mode,Sample Cache,Device ID,Object Type,Object Number,Property ID,COV Increment,Property,Property Type,Multiplier,Decimal Scale
Therm,Thermometer,,therm/1,0 * * * * *,BACnet/IP,Polling only,5000,3637469,analog-input,0,present-value,,temp,Instantaneous,1,5
,,,,,,,,3637469,analog-input,1,present-value,,tempWater,Instantaneous,1,5
,,,,,,,,3637469,analog-input,2,present-value,,tempOutdoor,Instantaneous,1,5
Meter,,,meter/1,0 * * * * *,BACnet/IP,Polling only,5000,112821,analog-input,0,present-value,,watts,Instantaneous,1,0
,,,,,,,,112821,accumulator,0,present-value,,wattHours,Accumulating,1,0Each component configuration contains the following settings:
| Setting | Description |
|---|---|
| Schedule | A cron schedule that determines when data is collected, or millisecond frequency. |
| Service Name | A unique name to identify this data source with. |
| Service Group | A group name to associate this data source with. |
| Source ID | The SolarNetwork unique source ID to assign to datum collected by this component. |
| BACnet Connection | The Service Name of the BACnet Connection component to use. |
| Sample Maximum Age | A maximum time to cache captured BACnet data, in milliseconds. |
| Persist Mode | Controls when to persist datum. Event modes relate to change-of-value subscription updates published by the associated BACnet devices. Polling modes relate to the schedule configured on this component. |
| Device Configurations | A list of BACnet device-specific settings. Any number of device configurations can be added, to collect data from any number of BACnet devices. |
- BACnet Connection
- This is the Service Name of the BACnet Connection component configured elsewhere in SolarNode. You must configure that component with the proper connection settings for your BACnet network, configure a unique Service Name on that component, and then enter that same Service Name here.
- Source ID
- This value unique identifies the data collected by this component, by this node, on SolarNetwork. Each configured component should use a different value.
- Sample Maximum Age
- SolarNode will cache the data collected from the BACnet device for at most this amount of time before refreshing data from the device again. Some devices do not refresh their values more than a fixed interval, so this setting can be used to avoid reading data unnecessarily. This setting also helps in highly dynamic configurations where other plugins request the current values from this component frequently.
You must configure settings for each BACnet device you want to collect data from. You can configure as many device settings as you like, using the + and - buttons to add/remove configurations.
Each device configuration contains the following settings:
| Setting | Description |
|---|---|
| Device ID | The BACnet device ID to collect data from. |
| Property Configurations | A list of BACnet object property-specific settings. Any number of property configurations can be added, to collect data from any number of object properties on the associated BACnet device. |
You must configure settings for each datum property you want to collect from a given device. You can configure as many property settings as you like, using the + and - buttons to add/remove configurations.
Each property configuration contains the following settings:
| Setting | Default | Description |
|---|---|---|
| Object Type | The BACnet object type to collect data from. Can be specified as a name, like analog-input or AnalogInput, or the associated integer code, like 0. |
|
| Object Number | The BACnet object type instance number to collect data from. | |
| Property ID | present-value |
The BACnet object property identifier to collect data from. Can be specified as a name, like present-value or PresentValue, or the associated integer code, like 85. |
| COV Increment | An optional decimal change-of-value (COV) event threshold to request when subscribing to COV events, essentially filtering the COV events unless the property value has changed by at least this amount. | |
| Property | The name of the datum property to save the BACnet value as. | |
| Property Type | Instantaneous |
The type of datum property to use. |
| Multiplier | 1 |
For numeric data types, a multiplier to apply to the BACnet property value to normalize it into a standard unit. |
| Decimal Scale | 5 |
For numeric data types, a maximum number of decimal places to round decimal numbers to, or -1 to not do any rounding. |
- COV Increment
- This value only affects the change-of-value (COV) event subscription, and has no impact on the polling schedule configured. This can be used to limit the number of COV events generated by highly-dynamic BACnet property values, so events are only generated if the value changes by at least this amount.
- Property
- Property names represent what the associated data value is, and SolarNetwork
has many standardized names that you should consider using. For example the
EnergyDatum
class defines properties such as
wattsandwattHoursfor electrical energy. - Property Type
- Each property must be categorized as
Accumulating,Instantaneous, orStatus. Accumulating is used for properties that record a value that accumulates over time, such aswattHourscaptured from a power meter. Instantaneous is used for properties that capture values that record independent values over time, such aswatts. Status is used for non-numeric values such as string status messages. - Multiplier
- The property values stored in SolarNetwork should be normalized into standard
base units if possible. For example if a power meter reports power in kilowattts
then a unit multiplier of
1000can be used to convert the values into watts. - Decimal Scale
- This setting will round decimal numbers to at most this number of decimal places. Setting
to
0rounds decimals to whole numbers. Setting to-1disables rounding completely.